Table 33: Motor Thermistor
Parameters
e30bb686.13
+24 V
+24 V
D IN
D IN
D IN
COM
D IN
D IN
D IN
+10
V
A IN
A IN
COM
A OUT
COM
12
13
18
19
20
27
29
32
33
50
53
54
55
42
39
A53
U - I
D IN
37
Drive
Function Setting
Parameter 1-90 Motor Thermal Protection [2] Thermistor trip
Parameter 1-93 Thermistor Source [1] Analog input 53
* = Default value
If only a warning is required, set parameter 1-90 Motor Thermal Protection to [1] Thermistor warn-
ing.
D IN 37 is an option.