DSE Model 5210 Automatic Start Engine Management and Instrumentation System Operators Manual
3 OPERATION
The following description details the sequences followed by a module containing the standard ā€˜factory
configuration’. Always refer to your configuration source for the exact sequences and timers observed by any
particular module in the field.
FIG 1
3.1 AUTOMATIC MODE OF OPERATION
NOTE:- If a digital input configured to panel lock is active, the LCD will display the
icon. When in panel lock, changing module modes will not be possible. Viewing the instruments and event logs
is NOT affected by panel lock.
This mode is activated by pressing the pushbutton. An LED indicator beside the button confirms this
action.
When a Remote Start signal is applied to the remote start input, the following sequence is initiated:-
The Remote Start Active indicator illuminates (if configured).
To allow for false signals the Start Delay timer is initiated. After this delay, if the pre-heat output option is selected
then the pre-heat timer is initiated, and the corresponding auxiliary output (if configured) will energise.
5210 OPERATING MANUAL ISSUE 2 21/05/2003 AM
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Deep Sea Electronics Plc 5210 and is the answer not in the manual?

Deep Sea Electronics Plc 5210 Specifications

General IconGeneral
BrandDeep Sea Electronics Plc
Model5210
CategoryController
LanguageEnglish

Related product manuals