Table 31. Particulate contamination specifications
Particulate contamination Specifications
Air filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit
NOTE: This condition applies to data center environments only. Air
filtration requirements do not apply to IT equipment designed to be
used outside a data center, in environments such as an office or
factory floor.
NOTE: Air entering the data center must have MERV11 or MERV13
filtration.
Conductive dust Air must be free of conductive dust, zinc whiskers, or other
conductive particles
NOTE: This condition applies to data center and non-data center
environments.
Corrosive dust
Air must be free of corrosive dust
Residual dust present in the air must have a deliquescent point less
than 60% relative humidity
NOTE: This condition applies to data center and non-data center
environments.
Table 32. Gaseous contamination specifications
Gaseous contamination Specifications
Copper coupon corrosion rate <300 Å/month per Class G1 as defined by ANSI/ISA71.04-2013
Silver coupon corrosion rate <200 Å/month as defined by ANSI/ISA71.04-2013
Thermal air restrictions
ASHRAE A3 environment
Two PSUs are required in redundant mode, however single PSU failure is not supported.
PCIe SSD is not supported.
DIMMs greater than 32 GB are not supported.
Both SW and DW GPGPU/FPGA are not supported.
CPU TDP greater than 200W are not supported.
Rear drives are not supported.
PCIe card TDP more than 25 W is not supported.
OCP is supported with 85C active optic cable.
ASHRAE A4 environment
Two PSUs are required in redundant mode, however single PSU failure is not supported.
PCIe SSD is not supported.
DIMMs greater than 32 GB are not supported.
Both SW and DW GPGPU/FPGA are not supported.
CPU TDP greater than 200W are not supported.
Rear drives are not supported.
PCIe card TDP more than 25 W is not supported.
OCP is supported with 85C active cable and cards Tier<=4
BOSS N1 is not supported.
Technical specifications
33