AH500 Programming Manual
2-44
Refresh time
SM1190
SM1190 is ON when the trigger is enabled and the last mail has
been sent in error.
SM1191
SM1191 is ON when the trigger is enabled and the mail has been
sent.
SM1192
SM1192 is ON when the trigger is enabled and there is an SMTP
server response timeout.
SM1193
SM1193 is ON when the trigger is enabled and there is an SMTP
server response error.
SM1194
SM1194 is ON when the trigger is enabled and the size of the
attachment exceeds the limit.
SM1195
SM1195 is ON when the trigger is enabled and the attachment is
not found.
SM1196 is ON when there is a socket configuration error.
↓
The flag is refreshed when the socket function is executed.
↓
Users set SM1374 to ON and reset it to OFF.
AH5×0
SM1392
↓
SM1423
SM1392 is ON when the PLC Link is enabled and the master
connects to slave 1~32.
AH5×1
SM1392 is ON when the COM1-Modbus connection is enabled
and the master connects to slave 1~32.
AH5×0
SM1424
↓
SM1455
SM1424 is ON when the PLC Link is enabled and the master
accesses the data in slave 1~32.
AH5×1
SM1424 is ON when the COM1-Modbus connection is enabled
and the master accesses data from slave 1~32.
AH5×0
SM1456
↓
SM1487
SM1456 is ON when the PLC Link is enabled and an error occurs
in the reading of the data from slave 1~32.
AH5×1
SM1456 is ON when the COM1-Modbus connection is enabled
and an error occurs in the reading of data from slave 1~32.
AH5×0
SM1488
↓
SM1519
SM1488 is ON when the PLC Link is enabled and an error occurs
in the writing of the data into slave 1~32.
AH5×1
SM1488 is ON when the COM1-Modbus connection is enabled
and an error occurs in the writing of data to slave 1~32.
AH5×0
SM1520
↓
SM1551
SM1520 is ON when the PLC Link is enabled and the master
finishes reading the data from slave 1~32.
AH5×1
SM1520 is ON when a Modbus connection is enabled for COM1
and the master finishes reading data from slave 1~32.
AH5×0
SM1552
↓
SM1583
SM1552 is ON when the PLC Link is enabled and the master
finishes writing the data into slave 1~32.
AH5×1
SM1552 is ON when a Modbus connection is enabled for COM1
and the master finishes writing data to slave 1~32.
Users set the flag ON and reset it OFF.
SM1588 is ON when the master detects the slaves.
SM1589 is ON when an error occurs.
SM1590 is ON when there is a device address error.
SM1591 is ON when there is a timeout.
SM1592 is ON when the number of polling cycles is incorrect.
Users set the flag to ON and reset it to OFF.
SM1596 is ON when there is an operation error in the PLC Link