ASRTU-EC16AP1TA EtherCAT Remote Communication Module Operation Manual
4-4
_4
ASRTU-EC16AP1TA Safety Circuit Wiring
AC power supply: 100240VAC; 50/60 Hz
Power supply circuit protection fuse
System circuit isolation device: The electromagnetic contactor, relay and other switch can be used as
the isolation device to prevent the system from becoming unstable when the power supply is
discontinuous.
Power indicator
Emergency stop button: The button cuts off the system power supply when an accidental situation
takes place.
Delta power module DVP-PS02 or AS-PS02A (24VDC)
ASRTU-EC16AP1TA device
Ground
Safety circuit
4.3.2 Ground
The diameter of the ground wire should not be less than the diameters of the wires connected to the
terminals L and N.
If using multiple pieces of equipment, do use a single-point ground.
ASRTU-EC16AP1TA
Another piece
of equipment
The single-point ground is better.