ASRTU-EC16AP1TA EtherCAT Remote Communication Module Operation Manual
8-2
_8
8.1 LED Indicator Diagnosis
POWER LED
POWER LED indicates if the power supply to ASRTU-EC16AP1TA is normal.
LED status Indication How to correct
Off
The power supply is abnormal.
Make sure that the power supply to
ASRTU-EC16AP1TA is normal
Green light on
The power supply is normal. --
Error LED
Error LED indicates if there is an error in ASRTU-EC16AP1TA and right-side modules.
LED status Indication How to correct
Off
ASRTU-EC16AP1TA works normally or
lacks the work power.
--
Red light
blinking
Possible causes:
1. The configuration data for
ASRTU-EC16AP1TA are invalid.
2.
The extension modules on the
right of ASRTU-EC16AP1TA are in
error.
3.
The modules configured on the
software are inconsistent with
those ac
tually connected on the
right of ASRTU-EC16AP1TA.
4. The EtherCAT communication of
ASRTU-EC16AP1TA is broken.
5. Firmware error and thus
ASRTU-EC16AP1TA’s firmware
online upgrade failure
1. Check if the actual modules on the right
of ASRTU-EC16AP1TA are consistent
with those configured on the software.
2. Check if the power supply and wiring of
the modules on the right of
ASRTU-EC16AP1TA are fine.
3. Check out the error information of the
modules on the right of
ASRTU-EC16AP1TA and then deal with
the errors by following the instructions in
corresponding module manuals.
4. Make sure that the connection of
EtherCAT cable is normal.
5. If the online upgrade of
ASRTU-EC16AP1TA’s firmware fails, you
can try to power it on again. If the
problem cannot be solved after you
repower it multiple times, contact local
technicians.
Red light on ASRTU-EC16AP1TA is under voltage
Check if the power supply for
ASRTU-EC16AP1TA works.
RUN LED
RUN LED indicates the communication status of ASRTU-EC16AP1TA in the EtherCAT network.
LED status Indication How to correct
Off
ASRTU-EC16AP1TA is in Init
status.
Check if the cable connection at the EtherCAT port of
ASRTU-EC16AP1TA is fine.
Green light
blinking
ASRTU-EC16AP1TA is not in
OP status.
1. Check if ASRTU-EC16AP1TA produces an alarm
(i.e. Error indicator ON or
blinking) and ensure that
no alarm occurs to right-side modules.
2. Ensure that the cable connection at the EtherCAT
port of ASRTU-EC16AP1TA is normal.
Green light on
ASRTU-EC16AP1TA is
communicating normally in the
EtherCAT network.
--