ASRTU-EC16AP1TA EtherCAT Remote Communication Module Operation Manual
2-4
Item Specification
Transmission medium Cat 5 or above shielded cable
Transmission distance 100 m
Topology structure Linear topology
Environmental Specification
Item Specification
Noise Immunity
ESD(IEC 61131-2, IEC 61000-4-2)
:
Contact Discharge
EFT(IEC 61131-2, IEC 61000-4-4)
: Power Line: 2KV, Digital
I/O: 1KV
Communication I/O: 2KV
Damped-Oscillatory Wave: Power Line: 1KV, Digital I/O: 1KV
RS(IEC 61131-2, IEC 61000-4-3): 80M Hz ~ 1000M Hz,
10V/m; 1400M Hz ~ 6000M Hz, 3 V/m
Operating temperature -20ºC ~ 60ºC
Storage temperature -40ºC ~ 80ºC
Operating humidity
Storage humidity
Pollution degree 2
Ingress protection
(IP ratings)
IP20
Vibration/shock resistance
Standard: IEC 61131-2, IEC 68-2-6 (TEST Fc)/IEC 61131-2 &
IEC 68-2-27 (TEST Ea)
Safety Conforms to IEC 61131-2, UL 61010-1, UL 61010-2-201
Barometric pressure-altitude
Operating: 1013 ~ 795 hPa (0 ~ 2000 m)
Storage: 1013 ~ 660 hPa (0 ~ 3500 m)
Flammability
rating of plastic case
UL94V-0
Weight
84 g