6-50
Modulon DPH Series
Bypass
POWER FLOW
Maintenance
Bypass
Bypass
Mains
Load
0 %
MEASUREMENT
Power Flow
UPS-1.1 SETUP
MAINTENANCE
Power Flow
Summary
System Status
2
WARNING
0 %
0 mins
LOG IN
Administrator
10:15
May 25,2018
Administrator Login
(Figure 6-70 : Bypass Mode Screen_ Administrator Login)
5
Click SETUP ĺMode Setting ĺOn-Line.
Bypass
UPS-1.1
MODE SETTING
MEASUREMENT
Mode Setting
SETUP
MAINTENANCE LOG IN
Administrator
On-Line Green ECO
Energy
Recycle
Frequency
Conversion
Select to change system mode
2
WARNING
10:15
May 25,2018
(Figure 6-71: Select On-Line Mode)
6
Switch OFF the UPS’s bypass switch (Q0) and Delta or non-Delta external maintenance
bypass cabinet’s input breaker or switch (Q1).
7
The UPS will shut down, and then, the LCD and the tri-color LED indicator will be off.