2-13
2
ௐ
ௐ
Introduction
Tri-color LED
Indicator
Status Meaning
Yellow ON
1. The UPS is running in bypass mode and the text
‘Bypass’ appears in the upper right corner of the
screen.
2. The UPS is running in battery mode and the text
‘Battery’ appears in the upper right corner of the screen.
3. The UPS is running in standby mode and the text
‘Standby’ appears in the upper right corner of the
screen.
4. The UPS is in the soft start status and the text ‘Softstart’
appears in the upper right corner of the screen.
5. The UPS is in the energy recycle status and the text
‘Energy Recycle’ appears in the upper right corner of
the screen.
6. There is a minor or medium warning and the buzzers
sound.
Warning Level Buzzer Frequency
Minor
The buzzers beep 0.5 second for
every three seconds.
Medium
The buzzers beep 0.5 second for
every second.
To clear the warning, please refer to 10. Troubleshooting.
Red ON
There is a major warning and the buzzers sound.
Warning Level Buzzer Frequency
Major Long beep
To clear the warning, please refer to 10. Troubleshooting.