Services Modbus gateway
IX10 User Guide
562
n
If connection_type is set to serial:
i. Set the serial port:
i. Use the ? to determine available serial ports:
(config service modbus_gateway client test_modbus_
client)> ... serial port ?
Serial
Additional Configuration
-------------------------------------------------------
------------------------
port1 Port 1
(config service modbus_gateway client test_modbus_
client)>
ii. Set the port:
(config service modbus_gateway client test_modbus_
client)> serial port
(config service modbus_gateway client test_modbus_
client)>
ii. Set the packet mode:
(config service modbus_gateway client test_modbus_client)>
serial packet_mode value
(config service modbus_gateway client test_modbus_client)>
where value is either rtu or ascii. The default is rtu.
iii. Set the maximum allowable time between bytes in a packet:
(config service modbus_gateway client test_modbus_client)>
serial idle_gap value
(config service modbus_gateway client test_modbus_client)>
where value is any number between 10 milliseconds and one second, and take
the format number{ms|s}.
For example, to set idle_gap to one second, enter 1000ms or 1s.
iv. (Optional) Enable half-duplex (two wire) mode:
(config service modbus_gateway client test_modbus_client)>
serial half_duplex true
(config service modbus_gateway client test_modbus_client)>
d. (Optional) Enable the gateway to send broadcast messages to this client: