EasyManua.ls Logo

Dräger P3U - Page 16

Dräger P3U
140 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connections
16
Connecting the Dräger Polytron 7000 transmitter to control units with
a 4 to 20 mA interfaced made by other manufacturers:
Further information about the connection can be found in the instructions for the
control unit being used.
Installing the transmitter in non-explosion-hazard areas:
When installing a transmitter in a non-explosion-hazard area, connect the cable
shield and the negative pole of the supply voltage to earth at the switch cabinet or
distribution panel.
Ensure that the supply voltage provided by the control unit (ignoring the load re-
sistance) is at least as high as specified in the tables of page 19 to page 21.
If digital communication in accordance with HART is to be used, the load resist-
ance of the supply unit must lie between 230 and 500 .
The permissible cable lengths are shown in the tables on page 19 to page 21. In
each case, use the line marked "Number of transmitters = 1".
Caution:
Remove the explosion-protection markings from the transmitter. Once the
transmitter has been used after installation in this manner, it may never be
installed in explosion-hazard areas. Explosion hazard!
01223758_1_en.eps
Non-explosion-hazard area
Control unit
4 ... 20 mA
0 V
+
+

Table of Contents

Related product manuals