Normally the Zone Alarm reporting codes will transmit a “3” as the event descriptor for most zone
types, to indicate a burglary alarm. However, if the zone type is a Standard Fire Zone, Delayed
Fire Zone or Auto Verify Fire Zone, the PC4010 will transmit a “1” as the event descriptor for these
zone types to indicate a fire alarm is being transmitted.
For zones programmed as momentary keyswitch arming or maintained keyswitch arming, the
PC4010 will transmit a “4” and the reporting code programmed in the “Zone Alarm” section to
indicate a closing (arming) of a partition.
In the Zone Restore reporting codes section, a zone will normally transmit a “9” as the event
descriptor for burglary or fire zones to indicate the zone has been restored. However, if the zone
has been programmed as a momentary or maintained keyswitch arming zone, when the zone is
used to disarm a partition it will transmit a “5” and the reporting code programmed in the zone
restoral section to indicate an opening (disarming) of a partition.
SYSTEM AREA
COMMUNICATOR
MAIN ITEMS
PC4010 Reporting Code Section Event
Descriptor
2 Wire Smoke Alarm Trouble 6
2 Wire Smoke Trouble Restore 9
2 Wire Smoke alarm 1
2 Wire Smoke Restore 9
2nd Master Close 4
2nd Master Open 5
4204 Aux Supply Trouble Alarm 6
4204 Battery Trouble Restore 9
4204 AC Trouble Alarm 6
4204 AC Trouble Restore 9
4204 Aux Supply Trouble Restore 9
Auto Arm Abort F
Automatic Opening 5
Automatic Closing 4
Buffer Near Full F
Cellular Trouble Restoral 9
Cellular Trouble F
Closing Access Codes 1 to 128 4
Closing Keyswitch 1 to 128 4
COMBUS Trouble Alarm 6
COMBUS Trouble Restoral 9
Downloading Lead In F
Downloading Lead Out F
Duress Code 2
Fire Zone Troubles 1 to 128 6
Ground Fault F
Ground Fault Restoral 9
Hold Up Alarm 2
Hold Up Restore 9
Installer’s Lead In 8
Installer’s Lead Out 8
Keypad [A] key Alarm 7
Keypad [F] key Alarm 1
Keypad [F] key Restore 9
Keypad [P] key Restore 9
Keypad [P] key Alarm 2
Keypad Lockout Code F
Keypad [A] key Restore 9
Links Test 0
Module Tamper Alarm F
Module Tamper Restoral 9
Opening After Alarm F
Opening Access Codes 1 to 128 5
Opening Keyswitch 1 to 128 5
Panic Restore 9
Panic Alarm 2
Partial Closing Code D
PC4010 Reporting Code Section Event
Descriptor
Partition Open 5
Partition Close 4
Periodic Test 0
Periodic UL Test 0
Police Restore 9
Police Alarm 3
Quick Arm Closing Code 4
RS 232 Trouble F
RS 232 Restore 9
System TLM Line 1 Trouble F
System Test 0
4204 Battery Trouble Alarm 6
System TLM Line 2 Trouble F
System TLM Line 2 Restore 9
System Bell Trouble Alarm 6
System Bell Trouble Restoral 9
System Aux Supply Trouble Restoral 9
System Aux Supply Trouble Alarm 6
System Battery Trouble Restoral 9
System Battery Trouble Alarm 6
System AC Trouble Restoral 9
System FTC Restoral 9
System AC Trouble Alarm 6
System TLM Line 1 Restoral 9
Technical Alarm 3
Technical Restore 9
Waterflow Trouble 6
Waterflow Trouble Restore 9
Waterflow Alarm 1
Waterflow Restore 9
Automation Fault 6
Automation Restore 9
Zone Sensor Fault Restore 9
Zone Sensor Fault 6
Zone Fault Restore 9
Zone Alarms 1 to 128 (All others) 3
Zone Low Battery 6
Zone Low Battery Restore 9
Zone Tamper Restoral 9
Zone Restorals 1 to 128 (All others) 9
Zone Alarms 1 to 128 (Fire Alarms) 1
Zone Fault 6
Zone Fault Restore 9
Zone Tamper 6
Zone Tamper Restore 9
DVAC Trouble 6
DVAC Trouble Restore 9