28
SYSTEM AREA
COMMUNICATOR
REPORTING CODES
Zone trouble and Zone Tamper reporting codes for zone 01 to 64. The only types of zone that will
cause a zone trouble are the Standard Fire, Delayed fire, Auto Verify Fire, Sprinkler Zone, and the
LINKS Supervisory Zones. Regardless of the EOL type being used these zone types will send the
programmed reporting code for a zone trouble condition. When using double EOL and an open
circuit condition occurs (Zone Tamper) the remaining zone types will send the programmed
reporting code as a Zone Tamper condition. This will include a zone tamper on a Wireless zone
(See RF Zone Options for details on the Wireless Zones).
Zone trouble and Zone Tamper Restoral reporting codes for zone 01 to 64. The only types of zone
that will cause a zone trouble restoral are the Standard Fire, Delayed fire, Auto Verify Fire,
Sprinkler Zone, and the LINKS Supervisory Zones. Regardless of the EOL type being used these
zone types will send the programmed reporting code for a zone trouble restoral condition. When
using double EOL and an open circuit restoral condition occurs (Zone Tamper restoral) the
remaining zone types will send the programmed reporting code as a Zone Tamper restoral
condition. This will include a zone tamper restorals on a Wireless zone (See RF Zone Options for
details on the Wireless Zones).
Zone Fault reporting codes for zone 01 to 64 . The following types of zone will not cause a zone
Fault are the Standard Fire, Delayed fire, Auto Verify Fire, Sprinkler Zone, LINKS Supervisory, and
Wireless Zones. When using double EOL and an Short circuit condition occurs (Zone Fault) the
remaining zone types will send the programmed reporting code as a Zone Fault condition.
Zone Fault Restoral reporting codes for zone 01 to 64 . The following types of zone will not cause
a zone Fault restoral are the Standard Fire, Delayed fire, Auto Verify Fire, Sprinkler Zone, LINKS
Supervisory, and Wireless Zones. When using double EOL and an short circuit restoral condition
occurs (Zone Fault restoral) the remaining zone types will send the programmed reporting code
as a Zone Fault restoral condition.
Zone Sensor Fault trouble reporting code for wireless zones 1 - 64. When a wireless zone has not
reported in to the PC4164 during the Zone Supervisory time then the panel will generate a “Zn
Sensor Fault” trouble and transmission.
Zone Sensor Fault trouble restoral reporting code for wireless zones 1 - 64. When a wireless zone
regains communication with the PC4164 then the panel will restore the “Zn Sensor Fault” trouble
and send the programmed reporting code.
Zone Low Battery trouble reporting codes for wireless zones 1 - 64. When a wireless zone sends a
zone low battery trouble condition to the PC4164 the main panel will generate a “Zn LwBatt Fault”
trouble and transmission.
Zone Low Battery trouble restoral reporting codes for wireless zones 1 - 64. When a wireless zone
sends a zone low battery restoral condition to the PC4164 the main panel will restore the “Zn
LwBatt Fault” trouble and send the programmed reporting code.
Reporting Codes for Tamper Alarms on Modules. All modules have a tamper zone, if the tamper is
activated.
There are 8 keypad tamper alarm reporting codes, one for each keypad that can be enrolled onto
the system.
There is an RS-232 tamper alarm reporting code.
There are 7 reporting codes for tamper alarms on 4108, 4116 and 4164 zone expansion modules.
ZONE TROUBLE
(02)
ZONE TROB.REST
(03)
ZONE FAULT
(04)
ZONE FAULT REST
(05)
ZONE SENSOR FLT
(06)
ZONE SEN FLT RES
(07)
ZONE LOWBAT ALARM
(08)
ZONE LOWBAT REST
(09)
MOD TAMP ALARM
(10)
LCD4500 KEYPADS
(0)
PC4400 RS-232
(1)
PC41XX ZONE EXP