31
• User System Test - When the user does a [Q][6] bell/comm test, the User System Test
reporting code is sent to the monitoring station to test communications. See “BELL/COMM
TEST” in the System Manual.
• Links Test - If this code is programmed and Links Test Transmission is enabled (see Links
Toggles), this reporting code will be sent via the Links unit. This code will never be sent
through the regular telephone line.
• Per. Test UL - Periodic Test Transmission U.L. This test transmission code is sent in place of a
Periodic Test Transmission if a Fire Trouble is present on the system at the time that the
periodic test transmission is supposed to be sent. The default reporting code is 99.
• DLS Lead In and DLS Lead Out - If the DLS Lead In reporting code is to be used, the DLS
callback feature must be enabled. (See DLS callback under DLS Toggles). When a computer
calls the PC4010 panel, after connection is made, both the panel and the computer will hang
up the telephone line. The panel will then transmit the DLS Lead In reporting code to the
monitoring station. The panel will then call the computer and begin downloading. When the
computer is finished downloading to the panel, they will both hang up the phone line, and the
PC4010 will transmit the DLS Lead Out reporting code to the monitoring station.
Note: DLS Lead In/Out reporting code is only sent for User Call Up and DLS Call Back.
• Ins Lead In and Ins Lead Out - The Installer's Lead In reporting code is sent to the monitoring
station when an installer enters the [Q][8] installer’s programming mode. The Lead Out code is
sent when the installer leaves [Q][8] installer’s programming.
• Automation Fault - This trouble condition will occur well the Escort 4580 losses
communication with the Automation Output control module. An audible trouble (VIA keypad
buzzer) will be generated as well as the trouble LED activating for the keypads. An Automation
Fault trouble reporting code will be sent to the monitoring station if programmed. If there is an
AC trouble present at the time the panel will not transmit the Automation Fault reporting code.
• Automation Restoral - This reporting code is sent when the Automation Fault trouble condition clears.
The PC4204 module maintenance reporting code section has reporting codes for sixteen
modules, with 6 codes for each module, in a total of 96 reporting codes. The 6 codes for each
module are Battery Trouble, AC Line Trouble, Aux Supply Trouble, Battery Restoral, AC Line
Restoral and Aux Supply Restoral. These reporting codes are similar to the system maintenance
reporting codes for the PC4010 main panel.
The PC4400 module maintenance reporting codes:
• RS-232 Trouble - This trouble is sent when the serial printer connected to the PC4400 module
goes off line, or when the PC4400 module loses communications with the serial printer.
• RS-232 Restore - The reporting code is sent when the RS-232 trouble condition restores.
• DVAC Trouble - This reporting code will be sent if the DVAC line is no longer present, if the self
diagnostics in the PC4400 module has failed or if DVAC communications has been shut down
by the central station.
• DVAC Restore - This reporting code will be transmitted when all of the DVAC trouble
conditions have been restored.
The Second System Grand Master Code used by the installer has a reporting code to report
when it has been used to arm a partition.
The Second System Grand Master Code used by the installer has a reporting code to report
when it has been used to disarm a partition.
The PC4700 Fire Module reporting codes:
• 2 Wire Alarm - This reporting code will be sent when there is a 2 Wire Smoke zone alarm
condition. The 2 Wire Smoke zone acts as a standard fire zone.
• 2 Wire Alarm Restore - This reporting code will be sent when there is a 2 wire smoke zone
alarm restoral occurs.
• Waterflow Alarm - This reporting code will be sent when there is a Waterflow zone alarm condition.
• Waterflow rest. - This reporting code will be sent when there is a Waterflow zone restoral occurs.
• 2 Wire Trouble - This trouble code will be sent when the 2 wire smoke detector zone has a
trouble (open) condition.
SYSTEM AREA
COMMUNICATOR
REPORTING CODES
LINKS MODULE
4204 MOD MAINT
(20)
4400 MOD MAINT
(21)
2ND MASTER CLOSE
(22)
2ND MASTER OPEN
(23)
4700 MODULE
(24)