53
PARTITION AREA
ADD/EDIT PAR
ZONE ASSIGNMENT
ADD/EDIT ZONES
Standard delay zones have an entry and exit delay. The exit delay starts as soon as the panel is
armed. The loop may be opened and closed during the delay time without causing an alarm. After
the exit delay time has expired, opening the loop will start the entry delay timer. During the entry
delay time, the keypad will sound steadily to advise the user that the system should be disarmed.
If the panel is disarmed before the entry time expires, no alarm will be generated.
The auxiliary delay zone operates the same way as the standard delay zone. However different
entry/exit times may be programmed. This is useful when a system has two delay zones, each
requiring a different entry/exit time.
The zone opened will activate instantly after the partition is armed and the exit delay has expired.
The zone will follow the entry time of a delay zone. If no delay zone has been tripped the zone will
activate instantly.
The zone will operate the same as the interior option with one exception: the zone will
automatically bypass if no delay zone on the partition is tripped during exit delay.
The zone will operate the same as the Interior Home/Away option with one exception: the zone
has entry delay.
A 24 Hour Bell zone is active at all times, and will create an alarm whether the partition is armed
or disarmed. This zone will not go into alarm if the zone is bypassed.
This zone operates like the 24 hour bell option except the bell output terminals are activated when
the partition is armed, and the keypad buzzer will be activated when the partition is disarmed.
Operates the same as the 24 hour bell, except this zone will only activate the keypad buzzer.
A fire zone is a 24 Hour zone that is specially used for fire detection circuits. On alarm, the bell
output will pulse the bells to indicate that the fire loop has been activated. The communicator will
immediately transmit the alarm to the monitoring station if a reporting code is programmed.
If the fire zone is open circuit, the keypads will beep every 10 seconds and a fire zone trouble will
be displayed on the LCD. If programmed the communicator will transmit the trouble to the
monitoring station. The keypad beeping may be silenced by pressing any key.
Note: Do NOT program fire zones as silent and do NOT use the double EOL resistors with
this zone type.
This fire zone works the same way as a 24 Hour fire zone, except the alarm memory and transmission
by the communicator is delayed by 30 seconds. If the alarm is acknowledged by pressing any key
before the 30 second delay expires, the bells will silence and the transmission will be aborted.
If after the alarm has been acknowledged, and the smoke detector has not been restored to normal,
after 90 seconds the bell output will be activated again, in which the user then has another 30 second
delay before the bell output latches and communicator are activated. A code would then be required
to silence the bell output.
Note: Do NOT program fire zones as silent and do NOT use the double EOL resistors with
this zone type.
Automatically Verifying Fire Zone.
This zone works the same way as the Standard Fire Zone with the exception that it will reset the
smoke detectors and wait for it to go into alarm again before sounding the bells and transmitting
the alarm to the monitoring station. If the smoke detectors do not go into alarm again, it assumes
there is a false alarm and no fire alarm will be initiated.
For activating an automatically verifying fire zone, the smoke detectors must be powered by the
SW AUX power supply on the main panel, or controlled by a relay on a PC4204 module.
Otherwise the PC4010 has no control over the power to the sensors.
When an automatically verifying fire zone is shorted, the PC4010 performs a “SENSOR RESET”,
which removes the power from the smoke detectors for 20 seconds. All SW AUX, BELL or PGM
outputs programmed for “SENSOR RESET” will be activated. The outputs will be deactivated for
20 seconds, regardless of the time programmed in the “PGM PULSE TIMES” section. After the 20
second reset pulse time, power will be restored to the sensors and all fire zone troubles will be
bypassed for 10 seconds to allow the detectors to settle.
DELAY HOME AWAY
(05)
24 HR BELL
(06)
24 HR BELL/BUZZ
(07)
24 HR BUZZER
(08)
STANDARD FIRE
(09)
DELAYED FIRE
(10)
AUTO VER FIRE
(11)
INSTANT
(02)
INTERIOR
(03)
INT HOME AWAY
(04)
STANDARD DELAY
(00)
AUXILIARY DELAY
(01)