54
PARTITION AREA
ADD/EDIT PAR
ZONE ASSIGNMENT
ADD/EDIT ZONES
If the smoke detectors initiate another alarm within 60 seconds after the power is restored, a fire
alarm will immediately sound and the monitoring station will be notified.
If the smoke detector is not reset during the sensor reset, the zone will not be restored. Because
the zone is not restored, a fire alarm will be initiated immediately.
See PGM OUTPUTS for programming an output as “SENSOR RESET”, “Smoke Detector Power
Supply” on the PC4204 Wiring Diagram for using the PC4204 to power up the smoke detectors,
and PC4010 Wiring Diagram in the System Manual for using the SW AUX on the main panel to
power up the smoke detectors.
Note: Do NOT program fire zones as silent and do NOT use the double EOL resistors with
this zone type.
A momentary closure of this zone will alternately arm and disarm the partition. This zone can be
used as a key switch to arm and disarm the system. The zone is monitored for EOL resistors if the
“ZONES EOL” option is enabled in the system options.
Notes: This zone type must not be used as a global zone.
When the zone is closed the partition will disarm. When the zone is opened the partition will be
armed. The zone is monitored for EOL resistors if the “ZONES EOL” option is enabled in the
system options.
The zone will operate the same as the 24 hour bell option with one exception: the installer’s mode
([Q][8]) must be entered before the system can be armed. This will ensure the problem has been
examined by the installer.
When this zone is tripped, the panel will instantly pick up the phone lines looking for a
downloading computer. Do not use this zone type to monitor for alarms.
“Links Supervisory” is used with the Links cellular communications unit to monitor for Links
troubles. When the Links PGM output activates, a Links trouble will be logged on the event buffer
and the zone trouble transmitted. This zone type may be programmed through the Links Toggle
Option section.
Note: If Partial Closings identify alarms are used the Alarm Reporting Code must be
programmed for the feature to function properly. Do NOT use the double EOL resistors with
this zone type.
It provides the Links with a forced answer for downloading purposes. This zone type may be
programmed through the Links Toggle Option section.
Note: Do NOT use the double EOL resistors with this zone type.
A Sprinkler zone is a 24 hour zone that is specifically used for sprinkler alarm circuits. On alarm,
the keypad buzzer will activate and the message “Sprinkler Zone In Alarm” will be displayed until
the zone has been restored. If enabled the communicator will immediately transmit the alarm to
the monitoring station if a reporting code is programmed. If the Sprinkler zone is open circuit the
keypads will beep every 10 seconds and a sprinkler supervisory trouble will be sent to the
monitoring station. The message “Fire Trouble !! <> To View” will be displayed until the zone has
been restored. Note: Do not use double EOL with the sprinkler zone.
This zone type is a 24 hour silent zone. This output does not activate Burg. outputs or the
Latched Strobe output (See Comms Format - for a list of Identifiers sent where applicable).
This zone type is a 24 hour silent zone. This output does not activate Burg. outputs or the
Latched Strobe output (See Comms Format - for a list of Identifiers sent where applicable).
This zone type is a 24 hour silent zone. This output does not activate Burg. outputs (See Comms
Format - for a list of Identifiers sent where applicable). Typical application of the zone is for
supervisory of equipment (i.e. Freezers).
MOMENTARY ARM
(12)
MAINTAINED ARM
(13)
LATCHING 24 HR
(14)
FORCED ANSWER
(15)
LINKS SUP
(16)
LINKS ANSWER
(17)
SPRINKLER
(18)
HOLD UP
(19)
PANIC
(20)
TECHNICAL
(21)