Table 2 – GSC400 Terminal Details
Terminal Wire Size
(AWG)
Current max.* Function
Crank 12 40A Crank Output Terminal
Battery +
3
12 40A Positive Battery Terminal
Battery -
3
12 40A Negative Battery Terminal
Fuel 12 40A Fuel Output Terminal
Extra Relay
1
12 40A
Configurable
1
Dry Contact
2
Extra Relay
Other side of Configurable Dry Contact
2
Speed 1 18 100mA Speed Signal Connection
Speed 2 18 100mA Speed Signal Connection
Quick Fit
Terminals
*Total controller current output (max 60A)
1
This is a configurable output. See Table 14 on page 64 for possible selections.
2
A normally open SPST relay with user access to both sides of the switch. This is
unlike the Fuel and Crank relay outputs which have one side connected internally
with battery positive and the opposite side accessible to the user.
3
Ensure wire gage is sufficient; otherwise (especially during cranking) there could
be a voltage drop across the cable to the controller from the battery causing the
GSC400 to display the wrong voltage and negatively affect the battery related
features of the controller.
Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
Ground 1 18 7mA Ground
Input 2 2 18 7mA Configurable (Low
Resistance, Gain of 1) *
Input 3 3 18 7mA Configurable (Low
Resistance, Gain of 3)
Input 4 4 18 7mA Configurable (Low
Resistance, Gain of 3)
Input 5 5 18 7mA Configurable (High
Resistance, Gain of 3)
Input 6 6 18 7mA Configurable (High
Resistance, Gain of 1) **
Input 7 7 18 7mA Configurable (High
Resistance, Gain of 3)
5V out *** 8 18 7mA Power for electronic
sensors. ***
Analog
Inputs
* LSB/LXB controllers only. For LS/LX controllers, this input spec is High
Resistance, Gain of 3.
** LSB/LXB controllers only. For LS/LX controllers this input has a gain of 3.
*** LSB/LXB controllers only. For LS/LX controllers this terminal is a ground.