Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
Input H -
GND
1 18 7mA
Configurable
1, 3
Input G -
GND
2 18 7mA
Configurable
1, 3
Input F -
GND
3 18 7mA
Configurable
1, 3
Input E -
GND
4 18 7mA
Configurable
1, 3
Input D -
BAT
5 18 7mA
Configurable
2, 3
Input C - BAT 6 18 7mA
Configurable
2, 3
Input B - BAT 7 18 7mA
Configurable
2, 3
Input A -
BAT
8 18 7mA
Configurable
2, 3
Emer. Stop 9 18 7mA Allows Manual
Emergency Stop (Open
= Active)
Start/Stop
(Remote Start
Contacts)
10 18 7mA Allows Manual
Start/Stop of Engine
(Active = Start, Inactive
= Stop)
Ground 11 18 7mA Ground
Ground 12 18 7mA Ground
Digital
Inputs
1
Ground input to generate logic high.
2
Tie input to battery + to generate logic high.
3
See Table 15 on page 67 for possible selections.
Terminal
Detail
Terminal
Location
Wire
Size
(AWG)
Current
max.
Function
+ V Bat 1 18 1.5A Positive Battery Voltage
Output A 2 18 200mA
Configurable*
Output B 3 18 200mA
Configurable*
Output C 4 18 200mA
Configurable*
Output D 5 18 200mA
Configurable*
Output E 6 18 200mA
Configurable*
Output F 7 18 200mA
Configurable*
Output G 8 18 200mA
Configurable*
Output H 9 18 200mA
Configurable*
+ V Bat 10 18 1.5A Positive Battery Voltage
Digital
Outputs*
*See Table 14 on page 64 for possible selections. These are sinking outputs (i.e.
switched to ground).