Over Volt Fail 4 650 VAC
Under Volt Warn 4 570 VAC
Under Volt Fail 4 550 VAC
A/C Current
Current source Enable
Turns Ratio 100A:5A
Over Current Warn 1 90 A
Over Current Fail 1 100 A
Over Current Warn 2 80 A
Over Current Fail 2 90 A
Over Current Warn 3 20 A
Over Current Fail 3 25 A
Over Current Warn 4 15 A
Over Current Fail 4 20 A
Engine Logic
Delay to Start 0 seconds
Pre-heat Time 0 seconds
Crank Time 15 seconds
MidHeat Time 0 seconds
Crank Rest Time 15 seconds
Crank Attempts 3
Fuel Crank Rest
Enable
False Restart
Enable
Post-Heat Time 0 seconds
ETS On Duration 0 seconds
Warm-up Time
600 seconds
Crank Disconnect
650 RPM
Cool Down Delay
0 seconds
Crank Oil pres
10 PSI
Digital Output Setup
All selections apply to
each individual output
Extra Relay Disable,
Output 1 Disable
Output 2 Disable
Output 3 Disable
Output 4 Disable
Output 5 Disable
Output 6
Disable
Output 7
Disable
Output 8
Disable
Exerciser setup
Exerciser Enable
Disable
Run Duration
30 minutes
Pre-Alarm Delay
5 minutes
Repeat Frequency
336 hours (14 days)
Start Hour
12
Start Date
8
Digital Input Setup
All selections apply to
each individual input
Input 1 (Bat)
Disable
Input 2 (Bat)
Disable
Input 3 (Bat)
Disable
Input 4 (Bat)
Disable
Input 5 (Gnd)
Disable
Input 6 (Gnd)
Disable
Input 7 (Gnd)
Disable