EasyManuals Logo

DynaGen GSC400 Series User Manual

DynaGen GSC400 Series
105 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #76 background imageLoading...
Page #76 background image
76 of 105
Over Volt Fail 4 650 VAC
Under Volt Warn 4 570 VAC
Under Volt Fail 4 550 VAC
A/C Current
Current source Enable
Turns Ratio 100A:5A
Over Current Warn 1 90 A
Over Current Fail 1 100 A
Over Current Warn 2 80 A
Over Current Fail 2 90 A
Over Current Warn 3 20 A
Over Current Fail 3 25 A
Over Current Warn 4 15 A
Over Current Fail 4 20 A
Engine Logic
Delay to Start 0 seconds
Pre-heat Time 0 seconds
Crank Time 15 seconds
MidHeat Time 0 seconds
Crank Rest Time 15 seconds
Crank Attempts 3
Fuel Crank Rest
Enable
False Restart
Enable
Post-Heat Time 0 seconds
ETS On Duration 0 seconds
Warm-up Time
600 seconds
Crank Disconnect
650 RPM
Cool Down Delay
0 seconds
Crank Oil pres
10 PSI
Digital Output Setup
All selections apply to
each individual output
Extra Relay Disable,
Output 1 Disable
Output 2 Disable
Output 3 Disable
Output 4 Disable
Output 5 Disable
Output 6
Disable
Output 7
Disable
Output 8
Disable
Exerciser setup
Exerciser Enable
Disable
Run Duration
30 minutes
Pre-Alarm Delay
5 minutes
Repeat Frequency
336 hours (14 days)
Start Hour
12
Start Date
8
Digital Input Setup
All selections apply to
each individual input
Input 1 (Bat)
Disable
Input 2 (Bat)
Disable
Input 3 (Bat)
Disable
Input 4 (Bat)
Disable
Input 5 (Gnd)
Disable
Input 6 (Gnd)
Disable
Input 7 (Gnd)
Disable

Table of Contents

Other manuals for DynaGen GSC400 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DynaGen GSC400 Series and is the answer not in the manual?

DynaGen GSC400 Series Specifications

General IconGeneral
BrandDynaGen
ModelGSC400 Series
CategoryController
LanguageEnglish

Related product manuals