F6 — Emergency Stop
Figure C-5: F6 — Emergency Stop
F6
Measured
voltage
OK ?
Yes
No
Check the reason for external fault
programmed to a digital input. Reset the fault
and start up the unit. Measure operating
voltage (+24V DC) from frequency converter.
Look at the monitoring page
for the digital input and measure
signal from external device.
If measured value
is OV=>
replace
external device
Check +24V circuit in converter
Replace defective parts as
recommended in spare parts lists
If measured value
is 24V and
monitored value
is OFF=>
replace I/O board
Clear fault memory