Checking the Cable and Motor Insulation
1. Check the motor cable insulation as follows:
Disconnect the motor cable from terminals U, V and W of the SVX9000/SPX9000 and
from the motor.
Measure the insulation resistance of the motor cable between each phase conductor as
well as between each phase conductor and the protective ground conductor.
The insulation resistance must be >1 M.
2. Check the input power cable insulation as follows:
Disconnect the input power cable from terminals L1, L2 and L3 of the SVX9000/
SPX9000 and from the utility line feeder.
Measure the insulation resistance of the input power cable between each phase
conductor as well as between each phase conductor and the protective ground
conductor.
The insulation resistance must be >1 M.
3. Check the motor insulation as follows:
Disconnect the motor cable from the motor and open any bridging connections in the
motor connection box.
Measure the insulation resistance of each motor winding. The measurement voltage
must equal at least the motor nominal voltage but not exceed 1000V.
The insulation resistance must be >1 M.