Table A-1: SVX9000/SPX9000 Drive Specifications (Continued)
Power Ratings
Table A-2: Output Power Ratings — 230V I
H
Insert a 1 for NEMA Type 1 or a 2 for NEMA Type 12 in place of the x in the
Catalog Number.
For SPX drives change SVX prefix to SPX.
Description Specification
Control Connections (Continued)
Analog Output 0(4) to 20 mA; R
L
max. 500; Resolution 10 bit; Accuracy ±2% or 0 to
10 V, R
L
1 k, select with jumper
Digital Outputs Open collector output, 50 mA/48V
Relay Outputs 3 programmable change-over relay outputs
Switching capacity: 24V DC / 8A, 250V AC / 8A, 125V DC / 0.4A
Minimum switching load: 5V/10 mA
Continuous capacity: < 2 A
rms
Protections
Overcurrent Protection Yes
Undervoltage Protection Yes
Ground (Earth) Fault In case of a ground fault in the motor or motor cables, only the
SVX9000/SPX9000 is protected
Input Phase Supervision Trips if any of the input phases are missing
Motor Phase Supervision Trips if any of the output phases are missing
Overtemperature Protection Yes
Motor Overload Protection Yes
Motor Stall Protection Yes
Motor Underload Protection Yes
Short Circuit Protection of the
+24V and +10V Reference
Voltages
Yes
Catalog Number

Frame
Size
Three-Phase Input
Horsepower Current
SVXF07Ax-2A_1 FR4 3/4 3.7
SVX001Ax-2A_1 1 4.8
SVXF15Ax-2A_1 1-1/2 6.6
SVX002Ax-2A_1 2 7.8
SVX003Ax-2A_1 3 11.0
SVX005Ax-2A_1 FR5 5 17.5
SVX007Ax-2A_1 7-1/2 25.
SVX010Ax-2A_1 FR6 10 31.
SVX015Ax-2A_1 15 48.
SVX020Ax-2A_1 FR7 20 61.
SVX025Ax-2A_1 25 75.
SVX030Ax-2A_1 30 88.