Environmental Requirements
Ensure that the environment meets the requirements listed in Table A-1 of Appendix A for
any storage or operating situation.
Table 2-2 specifies the minimum airflow required in the area where the drive will be
mounted.
Table 2-2: Cooling Airflow Requirements
Standard Mounting Instructions
1. Measure the mounting space to ensure that it allows for the minimum space
surrounding the drive. Drive dimensions are in Appendix A.
2. Make sure the mounting surface is flat and strong enough to support the drive, is not
flammable, and is not subject to excessive motion or vibration.
3. Ensure that the minimum airflow requirements for your drive are met at the mounting
location.
4. Mark the location of the mounting holes on the mounting surface, using the template
provided on the cover of the cardboard shipping package.
5. Using fasteners appropriate to your drive and mounting surface, securely attach the
drive to the mounting surface using all 4 screws or bolts.
Drive Type Cooling Air Required
230V, 3/4 – 3 hp I
H
480V, 1 – 5 hp I
H
41 cfm (70 m
3
/h)
230V, 5 – 7-1/2 hp I
H
480V, 7-1/2 – 15 hp I
H
112 cfm (190 m
3
/h)
230V, 10 – 15 hp I
H
480V, 20 – 30 hp I
H
575V, 2 – 25 hp I
H
250 cfm (425 m
3
/h)
230V, 20 – 30 hp I
H
480V, 40 – 60 hp I
H
575V, 30 – 40 hp I
H
250 cfm (425 m
3
/h)
480V, 75 – 125 hp I
H
575V, 60 – 75 hp I
H
383 cfm (650 m
3
/h)
480V, 150 – 200 hp I
H
575V, 100 – 150 hp I
H
765 cfm (1300 m
3
/h)