9000X AF Drives User Manual
MN04001004E
For more information visit: www.eaton.com C-13
June 2009
F14 — Frequency Converter Over Temperature
Figure C-13: F14 — Frequency Converter Over Temperature
F14 ?
No
Yes
Clear blocked heat sink by blowing
compressed air along fins of the heat sink
No
Value V1.9 =
Tam b ient ?
Yes
Read value of operation
temperature V1.9
F14
Check operation of cooling fans;
rotation and direction of blowing
Check the temperature measuring
circuit according to instructions in
service manual. Replace parts as
recommended and listed in spare
parts lists. Check control module using
instructions in service manual and
functional test using the 9000XSERVICE tool.
Clear fault memory