UL Compatible Cable Selection and Installation
Use only copper wire with temperature rating of at least 75°C.
Table 3-2: 40°C Cable and Fuse Sizes — 230V Ratings
UL recognized type JJS preferred but RK acceptable.
I
L
hp
Frame
Size NEC I [A] I [A]
Fuse
Quantity
Fuse
[A]
Wire Size Terminal Size
Power Ground Power Ground
1
1-1/2
2
3
FR4 4.2
6
6.8
9.6
4.8
6.6
7.8
11
3
3
3
3
10
10
10
15
14
14
14
14
14
14
14
14
16 – 12
16 – 12
16 – 12
16 – 12
16 – 14
16 – 14
16 – 14
16 – 14
5
7-1/2
10
FR5 15.2
22
28
17.5
25
31
3
3
3
20
30
40
12
10
8
12
10
8
16 – 8
16 – 8
16 – 8
16 – 8
16 – 8
16 – 8
15
20
FR6 42
54
48
61
3
3
60
80
4
2
8
6
14 – 0
14 – 0
10 – 2
10 – 2
25
30
40
FR7 68
80
104
72
87
114
3
3
3
100
110
125
2
1
1/0
6
6
4
14 – 0
14 – 0
14 – 0
10 – 00
10 – 00
10 – 00
50
60
75
FR8 130
154
192
140
170
205
3
3
3
175
200
250
3/0
4/0
300
2
0
2/0
4 – 3/0
000 – 350 MCM
000 – 350 MCM
4 – 000
4 – 000
4 – 000
100 FR9 248 261 3 300 2x4/0 3/0 2x000 – 350 MCM 4 – 000