EasyManua.ls Logo

Eaton 9000X - Table 3-3: 40°C Cable and Fuse Sizes - 480 V Ratings

Eaton 9000X
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9000X AF Drives User Manual
MN04001004E
For more information visit: www.eaton.com 3-3
June 2009
Table 3-3: 40°C Cable and Fuse Sizes — 480V Ratings
UL recognized type JJS preferred but RK acceptable.
I
L
hp
Frame
Size NEC I [A] I [A]
Fuse
Quantity
Fuse
[A]
Wire Size Terminal Size
Power Ground Power Ground
1-1/2
2
3
5
7-1/2
FR4 3
3.4
4.8
7.6
11
3.3
4.3
5.6
7.6
12
3
3
3
3
3
10
10
10
10
15
14
14
14
14
12
14
14
14
14
14
16 – 12
16 – 12
16 – 12
16 – 12
16 – 12
16 – 14
16 – 14
16 – 14
16 – 14
16 – 14
10
15
20
FR5 14
21
27
16
23
31
3
3
3
20
30
35
10
10
8
12
10
8
16 – 8
16 – 8
16 – 8
16 – 8
16 – 8
16 – 8
25
30
40
FR6 34
40
52
38
46
61
3
3
3
50
60
80
6
4
2
8
8
6
14 – 0
14 – 0
14 – 0
10 – 2
10 – 2
10 – 2
50
60
75
FR7 65
77
96
72
87
105
3
3
3
100
110
125
2
1
1/0
6
6
4
14 – 0
14 – 0
14 – 0
10 – 00
10 – 00
10 – 00
100
125
150
FR8 124
156
180
140
170
205
3
3
3
175
200
250
3/0
4/0
300
2
0
2/0
4 – 3/0
000 – 350 MCM
000 – 350 MCM
4 – 000
4 – 000
4 – 000
200
250
FR9 240
302
261
300
3
3
350
400
2x4/0
2x250
3/0
300
2x000 – 350 MCM
2x000 – 350 MCM
4 – 000
4 – 000
300
350
400
FR10 361
414
477
385
460
520
3
3
3
450
500
600
2x250
2x300
2x400
300
300
350
600 MCM
600 MCM
600 MCM
300 MCM
300 MCM
300 MCM
500
550
600
FR11 590
NS
NS
590
650
730
6
6
6
350
400
450
2x500
4x4/0
4x250
500
500
600
Bus Bar
Bus Bar
Bus Bar
Bus Bar
Bus Bar
Bus Bar
650
700
800
FR12 NS
NS
NS
820
920
1030
6
6
6
500
500
600
4x300
4x300
4x350
600
600
Bus Bar
Bus Bar
Bus Bar
Bus Bar
Bus Bar
Bus Bar

Table of Contents