EasyManua.ls Logo

Eaton 9000X - Page 81

Eaton 9000X
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9000X AF Drives User Manual
MN04001004E
For more information visit: www.eaton.com A-3
June 2009
Table A-1: SVX9000/SPX9000 Drive Specifications (Continued)
Description Specification
Control Characteristics
Control Method SVX Frequency Control (V/f)
SVX Open Loop Sensorless Vector
SPX Open Loop Sensorless Vector Control
SPX Closed Loop Control
Switching Frequency Adjustable with Parameter 2.6.9
208 – 230V: 3/4 – 15 hp: 1 to 16 kHz; default 10 kHz
20 – 30 hp: 1 to 10 kHz; default 3.6 kHz
380 – 500V: 1 – 30 hp: 1 to 16 kHz; default 10 kHz
40 – 200 hp: 1 to 10 kHz; default 3.6 kHz
525 – 690V All Sizes: 1 to 6 kHz; default 1.5 kHz
Frequency Reference Analog Input: Resolution 0.1% (10-bit), accuracy ±1%
Panel Reference: Resolution 0.01 Hz
Field Weakening Point 30 to 320 Hz
Acceleration Time 0.1 to 3000 sec.
Deceleration Time 0.1 to 3000 sec.
Braking Torque DC brake: 15% to 150% x T
n
(without brake option)
Environment
Ambient Operating Temperature 14°F (-10°C), no frost to 122°F (+50°C)
Storage Temperature -40°F (-40°C) to 158°F (70°C)
Relative Humidity 0 to 95% RH, non-condensing, non-corrosive, no dripping water
Air Quality Chemical vapors: IEC 60721-3-3, unit in operation, class 3C2
Mechanical particles: IEC 60721-3-3, unit in operation, class 3S2
Altitude 100% load capacity (no derating) up to 3300 ft. (1000m);
1% derating for each 330 ft. (100m) above 3300 ft. (1000m);
max. 10000 ft. (3000m)
Vibration EN 50178, EN 60068-2-6
5 to 50 Hz, displacement amplitude 1 mm (peak) at 3 to 15.8 Hz,
Max. acceleration amplitude 1 G at 15.8 to 150 Hz
Shock EN 50178, EN 60068-2-27
UPS Drop test (for applicable UPS weights)
Storage and shipping: max. 15 G, 11 mS (in package)
Enclosure Class NEMA 1/IP21 available all ratings
NEMA 12/IP54 available all ratings
Standards
EMC (at default settings) Immunity: Fulfils all EMC immunity requirements
Emissions: EN 61800-3
Safety UL 508C
Product IEC 61800-2
Control Connections
Analog Input Voltage 0 to 10V, R – 200 k differential (-10 to 10V joystick control)
Resolution 0.1%; accuracy ±1%
Analog Input Current 0(4) to 20 mA; R
i
– 250 differential
Digital Inputs (6) Positive or negative logic; 18 to 24V DC
Auxiliary Voltage +24V ±15%, max. 250 mA
Output Reference Voltage +10V +3%, max. load 10 mA