CAUTION
Only qualified service personnel knowledgeable of batteries and the required
precautions are allowed to do the installation or service work on batteries. Keep
unauthorized personnel away from the batteries. Before you install or replace
batteries, consider all the warnings, cautions, and notes concerning appropriate
handling. Do not disconnect the batteries when the UPS is in Battery mode.
Make sure that your replacement batteries are of the same number and type as
the battery that was originally installed in the UPS. See more accurate
instructions on the UPS.
Before you connect or disconnect battery terminals, disconnect the charging
source by opening the corresponding battery circuit breaker.
If the battery is inadvertently grounded, remove the source of the ground. All
batteries in all UPS models are ungrounded.
Discard batteries according to your local disposal requirements. Do not dispose
of batteries in a fire. When exposed to flame, batteries may explode.
To ensure proper cooling airflow and to protect personnel from dangerous
voltages inside the unit, keep the UPS door closed and the front panels
installed.
Do not install or operate the UPS system close to gas or electric heat sources.
Keep the operating environment within the parameters stated in this document.
CAUTION
Keep the surroundings of the UPS uncluttered, clean, and free from excess
moisture.
Obey all DANGER, CAUTION, and WARNING notices affixed to the equipment.
CAUTION
To prevent damage to the wiring channel and the wiring configuration in the
UPS cabinet base when lifting or moving the cabinet, use only the left or right
forklift slot to lift and move a packed cabinet.
Make sure that the forklift fork is inserted into the forklift slot at the horizontal
position. Do not tilt the fork upwards.
Insert the forks all the way through the base.
Failure to comply with these instructions may cause damage to the wiring
channels and the wiring configuration.
22..22 RReeccyycclliinngg tthhee uusseedd UUPPSS oorr bbaatttteerriieess
Remove the battery bank before you discard the UPS or its battery cabinet. Obey the local requirements
regarding battery recycling or disposal.
EATON 93T USER’S AND INSTALLATION GUIDE 614-40270
-
December 2023 www.eaton.eu 1122