NOTE: Do not connect battery strings with a different number of cells
in parallel.
15 kVA: 1x36 blocks, 9 Ah
20 kVA: 2x32 blocks, 7 Ah
30 kVA: 2x36 blocks, 9 Ah
40 kVA: 3x32 blocks, 9 Ah
60 kVA: 4x40 blocks, 9 Ah
80 kVA: 5x40 blocks, 9 Ah
Charging configuration ABM or float charge
End-of-discharge voltage 1.67 VPC
Charging current
15 kVA maximum: 15 A, configurable
20 kVA maximum: 20 A, configurable
30 kVA maximum: 30 A, configurable
40 kVA maximum: 40 A, configurable
60 kVA maximum: 60 A, configurable
80 kVA maximum: 80 A, configurable
Battery startup Available
Battery environment
Discharging temperature: -20 ... +50
Charging temperature: +0 ... +40
Storage temperature: -15 ... +40
Recommended operating and storage temperature: +25
99..77 EEnnvviirroonnmmeenntt
Table 24. Environmental specifications
Operating temperature +0 ... +40
The recommended operating temperature is +25 .
The system derates at +40 ... +50 .
Storage ambient temperature -25 ... +55 (-13 ... 131 ) when stored in the protective
packaging materials.
Operating altitude The UPS operates correctly below the altitude of 1,000 m (3,300 ft).
If the UPS is operated at an altitude above 2,000 m (6,600 ft),
contact your local service representative for more information.
Relative humidity (storage and
operating)
5 % 95 %, condensation free
Make sure that there is a temperature difference of at least 1
(1.8 °F) between the dry bulb and the wet bulb of the hygroscope to
avoid condensation.
Acoustic noise at 1 meter
15–20 kVA UPS: 55 dB
EATON 93T USER’S AND INSTALLATION GUIDE 614-40270
-
December 2023 www.eaton.eu 9977