99..55 UUPPSS oouuttppuutt
Table 22. 93T UPS output specifications
Output phases 3 phases + neutral
Rated output voltage
220/380 V
230/400 V
240/415 V
Configurable
Total harmonic voltage
distortion (THD)
100 % linear load: < 2 %
100 % non-linear load: < 5 %
Rated output frequency 50 Hz or 60 Hz, configurable
Rated output frequency
accuracy
±0.1 Hz
Overload capacity
102–110 % load: 60 min
111–125 % load: 10 min
126–150 % load: 1 min
> 151 % load: 150 ms
Output current
See Table .
Short circuit capability
(200 ms)
15–20 kVA UPS: 73 A
30 kVA UPS: 108 A
40 kVA UPS: 145 A
60 kVA UPS: 217 A
80 kVA UPS: 290 A
Rated load power factor 1.0
Load power factor (allowed) Lag 0.7 to lead 0.7
99..66 BBaatttteerryy
CAUTION
In case of connecting with an external battery, the neutral wire of the battery
must be included.
Table 23. Battery specifications
Battery type VRLA, 13 VDC
Battery voltage
320–607 VDC with external batteries
468–520 VDC (36-40 blocks) with internal batteries