Figure 24. Communication interfaces
1. MiniSlot 1
2. MiniSlot 2
3. Battery startup/switch to bypass
4. External battery trip
5. USB
6. RS232
7. Dry contact input (CN12)
8. Emergency power-off (EPO) and
CAN terminal (CN10)
55..44..11 CCNN1100
Terminal CN10 can be used to connect the parallel CAN communication signal and the remote emergency
power-off (REPO) signal.
Figure 25. CN10 terminal layout
1. Parallel signal +/-
2. Parallel signal +/-
3. NULL
4. NO_EPO_POWER
5. EPO_IN
6. EPO_GND
7. NC_EPO_POWER
8. CAN_GND
9. CAN-H parallel communication
10. CAN-L parallel communication
11. Pull-chain -, parallel back control
signal
12. Pull-chain +, parallel back control
signal