Figure 27. Connections of the EPO switch
A Normally open. When pins 5 and 6 are closed, the UPS performs an emergency power-off. Pins
7 and 8 are idle.
B Normally closed. Pins 5 and 6 are connected with a jumper cable. Keep the pins connected.
When pins 7 and 8 are open, the UPS performs an emergency power-off.
55..44..44 BBaatttteerryy ssttaarrttuupp//sswwiittcchh ttoo bbyyppaassss
The battery startup/switch to bypass button is used to start the UPS on battery power and transfer the
UPS to Bypass mode.
For the instructions on how to start the UPS on battery power, refer to Section
6.3.3 Battery start.
55..44..55 MMiinniiSSlloott ccaarrddss
The Eaton 93T UPS has two MiniSlot communication bays. The UPS is compatible with the following
MiniSlot cards:
GGiiggaabbiitt NNeettwwoorrkk CCaarrdd
Figure 28. Gigabit Network Card
The second-generation Gigabit Network Card is the new generation network communication card for
connecting the UPS with Ethernet and Internet. The new generation network communication card has
many novel features. The remarkably increased network communication speed and the confidentiality
protocol can provide emergency power-off, data saving, and other services to authorized IT personnel.