Figure 41. Password verification
Table 14. Control page functions
Control
function
Description
System Transfer to Bypass mode, start up the system, shut down the system, enable ESS, or
disable ESS. At the top of the page you can view the UPS status and the battery status.
UPS Perform a battery test, turn on the battery charger, turn off the battery charger, turn on a
single UPS, or turn off a single UPS. At the top of the page you can view the UPS status
and the battery status.
UPM View the UPM status, the UPS status, and the battery status, or shut down the UPM.
SSyysstteemm
On the System page you can transfer to Bypass mode, start up the system, shut down the system, enable
ESS, or disable ESS. A gray icon indicates that the function is unavailable. At the top of the page you can
view the UPS status and the battery status.
To transfer the system to Bypass mode:
NOTE: When the Go To Bypass icon is not gray, you can transfer to Bypass mode.
1. Select Go To Bypass to access the bypass page.
2. Select Go to Bypass.
3. Select OK to transfer to Bypass mode.
These instructions apply to the other functions, as well.
EATON 93T USER’S AND INSTALLATION GUIDE 614-40270
-