98 Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Table 13. User Settings (Continued)
Description
Available Settings Default Setting
Relay Config
Relay: [Alarm-1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/2/3/4]
Setup: [On Battery] [Summary Alarm] [On Bypass] [UPS OK]
[custom] [empty]
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS OK
#2: On Bypass
#3: Summary Alarm
#4: On Battery
Signal Inputs
Signal: [X-Slot-1] [X-Slot-2] [INPUT 1] [INPUT 2]
[signal inputs]
Logic: [0] [1]
For more information See “Programmable Signal Inputs” on
page 115.
<empty>
[1]
Serial Port Config
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
19200
Parallel Operation Settings
Parallel Operation Mode:
[Redundant Mode] [Capacity Mode]
This setting is not available for six-unit systems (must be
Redundant Mode only).
Redundant Mode
Parallel XCP: [System] [Sub Unit]
Select Sub Unit for PowerVision
®
software. Select System
for other software.
System
Auto ID Restart: [Done] [Restart]
Select Restart to reinitialize auto identification see “Auto
identification” on page 120.
None
Battery Setup
Number of EBMs: [0 through 4] See “Configuring for EBMs”
on page 107.
(See “Configuring the UPS for EBMs” on page 104.)
0
(means internal batteries only)
Battery Low Alarm Level: [1.750 through 1.950 volts per cell]
See “Setting The Battery Low Alarm Level” on page 108.
1.880 V/cell
(provides approximately 2.5 min
warning for the UPS)
Automatic Battery Tests: [Enabled] [Disabled] See
“Automatic Battery Test” on page 109.
Enabled
(automatically runs the battery
test once a month)
External Battery Capacity: Set Watts per cell
Use this setting only with customer-supplied external
batteries and the External Battery Interconnect. See
“Configuring the UPS for Customer Supplied Batteries” on
page 108.
None
Power Strategy
[High Efficiency] [Standard]
For more information, see Operating Modes the following
section.
High Efficiency
Start Screen
Eaton logo
Mimic screen
Eaton logo
User Settings