EasyManua.ls Logo

Eaton BladeUPS - How to Replace UPS Internal Batteries

Eaton BladeUPS
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 123
77..77 HHooww ttoo RReeppllaaccee UUPPSS IInntteerrnnaall BBaatttteerriieess
CAUTION
The UPS internal batteries are heavy (see page 140 ). Each battery tray holds two rows of five batteries.
Use caution when handling the heavy battery trays.
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull them
out of the UPS.
To replace the battery trays in the UPS cabinet:
1. Verify that the battery circuit breaker is in the OFF (O) position (Figure 60 ).
2. Remove the UPS front cover and set it aside (see Figure 83 ):
Figure 83. Removing the UPS Front Cover
LCD Cable
NOTE Disconnecting the control panel from the electronics module automatically transfers the
UPS to Bypass mode.
3. Remove the eight screws on the battery cover plate and retain. Remove the plate. See Figure 84 .
How to Replace UPS Internal Batteries

Table of Contents

Other manuals for Eaton BladeUPS

Related product manuals