124 Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Figure 84. Removing the UPS Battery Cover Plate
CAUTION
The UPS internal batteries are heavy. Each battery tray holds two rows of five batteries. Use caution when
handling the heavy battery trays.
Pull the battery trays out onto a flat, stable surface. The battery trays are unsupported when you pull them
out of the UPS.
4. Untuck the plastic handle at the end of a battery tray. Pull the handle firmly to remove the tray. Use both
hands to support the tray as it leaves the UPS cabinet. Repeat for each battery tray. See
7.11 Recycling the Used Battery or UPS for proper disposal.
5. Slide the new battery trays into the cabinet (see Figure 85 for two battery string installations and for
single-string installations). Verify that each tray is properly aligned before sliding in the tray
NOTE When installing single-string battery trays for BladeUPS 5.0 kVA, always install the
single-string trays in the bottom battery compartment.
6. When a tray is fully installed, tuck the plastic handle on the end of the tray into place.
Figure 85. Installing the UPS Battery Trays (Two Battery Strings)
How to Replace UPS Internal Batteries