Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 73
Figure 59. Example EBM Installations in Parallel Systems
Optional
Battery
Extension
Cables
44..1122 SSttaannddaalloonnee UUPPSS IInnssttaallllaattiioonn
NOTE Do not make unauthorized changes to the UPS; otherwise, damage may occur to your
equipment and void your warranty.
The UPS requires a dedicated branch circuit that meets the following requirements:
• Circuit with overcurrent protection as follows:
– 50A (BladeUPS 12 model)
– 30A (BladeUPS 12i or BladeUPS 8 model)
Standalone UPS Installation