Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 99
Table 13. User Settings (Continued)
Description
Available Settings Default Setting
User Password
[Enabled] [Disabled]
If Enabled is selected, the password is USER.
Disabled
Audible Alarms
[Normal Sound] [Disabled] Normal Sound
Unsynchronized Transfer to
Bypass
[Allowed] [Not Allowed]
Not Allowed
Transfer to Bypass When
Overload
[After a delay] [Immediately] After a delay
Automatic Start Delay
-1 through 32767 seconds
(-1 means disabled)
0s
Control Commands from X-
Slot1
Control Commands from X-
Slot2/Serv
[Allowed] [Disabled]
Selecting Disabled prevents load commands such as Load
Off through the X-Slot, including remotely.
Allowed
X-Slot Signal Input Activation
Delay
0 through 65 seconds
5s
Site Wiring Fault Notice [Enabled] [Disabled]
Alarm Enabled
Input Range
[Standard] [ITIC} Standard
Reset Custom Event Settings 0 through 32 Total: 0/32
REPO Configuration [Enabled][Disabled]
Enabled
SEE NOTE
Delayed Rectifier
Startup Settings
Group number: 0 through 10 (integers only);
Delay in seconds: 2 through 5 sec (integers only)
0 (Zero disables this feature)
5
NOTE Delayed rectifier startup increases existing delays for utility outages. This will allow a maximum of 50 seconds of
additional delay before starting the Rectifier and thus transferring the load to the rectifier feed.
When the group number is changed, the delay is determined by (Group #) * (Delay Value) = Delay in seconds. An RT unit
would return the load to utility after the delay. After the delay, a parallel unit would have the lowest unit ID return to
utility and subsequent units would return using a brief delay. The group and delay settings will be synchronized across all
parallel units
When the group number is changed, the delay is determined by (Group #) * (Delay Value) = Delay in seconds. An RT unit
would return the load to utility after the delay. After the delay, a parallel unit would have the lowest unit ID return to
utility and subsequent units would return using a brief delay. The group and delay settings will be synchronized across all
parallel units
55..66 OOppeerraattiinngg MMooddeess
The BladeUPS module front panel indicates the UPS status through the UPS indicators. See Figure 72.
Normal Mode
The BladeUPS module front panel indicates the UPS status through the UPS indicators.
Operating Modes