Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14 121
CChhaapptteerr 77 UUPPSS MMaaiinntteennaannccee
77..11 UUPPSS MMaaiinntteennaannccee
This chapter explains how to:
• Care for the UPS and batteries
• Replace the UPS batteries and EBMs
• Test new batteries
• Replace the electronics module
• Replace a UPS in a parallel system
• Recycle used batteries or UPS
• Update the UPS firmware
77..22 UUPPSS aanndd BBaatttteerryy CCaarree
For the best preventive maintenance, keep the area around the UPS clean and dust-free. If the atmosphere is
very dusty, clean the outside of the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of 25°C (77°F).
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service life
varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace
batteries at least every 5 years to keep units running at peak efficiency.
77..33 SSttoorriinngg tthhee UUPPSS aanndd BBaatttteerriieess
If you store the UPS for a long period, recharge the battery every six months by connecting the UPS to utility
power. The batteries charge to 80% capacity in fewer than five hours. However, Eaton recommends that the
batteries charge for 48 hours after long-term storage.
Check the battery recharge date on the shipping carton label. If the date has expired and the batteries were
never recharged, do not use the UPS. Contact your service representative.
77..44 WWhheenn ttoo RReeppllaaccee BBaatttteerriieess
When the
indicator flashes slowly and the audible alarm beeps intermittently, the batteries may need
replacing. Contact your service representative to order new batteries.
77..55 RReeppllaacciinngg BBaatttteerriieess
NOTE DO NOT DISCONNECT the batteries while the UPS is in Battery mode.
Batteries can be replaced easily without turning the UPS off or disconnecting the load.
If you prefer to remove input power to change the batteries, see section 5.12“Individual Paralleled UPS
Shutdown.
Consider all warnings, cautions, and notes before replacing batteries.