36 Eaton BladeUPS 5 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 14
Figure 17. Removing the Top Entry Conduit Landing Plate
Top Entry
Ferrite Assembly (mounted)
Conduit Landing Plate
7. Use a Greenlee
®
punch to provide one or more holes in the conduit landing plate to accommodate the
input and output wiring for the system.
8. Replace the conduit landing plate.
9. Replace the top entry wireway access cover:
Replace the cover in the recessed opening.
Replace the four bolts that secure the cover.
Figure 18. BladeUPS Bar Top Entry Terminal Block
Ground
Top Entry Terminal Block
Top Entry Installation