9 Menus
9.7.2.1 Circuit status of ZB-S in line 2
Priority
high 1 Luminaire-search mode AC
2 Luminaire-search mode DC
3 Circuit-learn mode AC
4 Circuit-learn mode DC
5 Durationtest mode
6 Functiontest mode AC
7 Functiontest mode DC
8 Battery mode
(Battery emergency light)
9 Mains mode
10 Normal operation mode
low 11 block
9.7.2.2 Circuit failure of ZB-S in line 3
Priority
high 1 DC fuse
2 AC fuse
3 Luminaire failure DC
4 if the measured current of last DC functiontest dif-
fers more than thepermitted difference of learned
DC measured current, which is set up at the device
(list < lsoll)
5 ISO Failure Plus
6 ISO Failure Minus
7 Luminaire failure AC
8 if the measured current of last AC functiontest dif-
fers more than the permitted difference of learned
AC measured current, which is set up at the device
(list < lsoll)
9 if battery voltage of the circuit is
low under the deep discharge sill
During communication with the system, «Please wait...» is
displayed. If there is an error, the faulty communication pro-
cess is automatically repeated. The read process then lasts
somewhat longer.