6 Parameters
6.2 Digital and analog inputs
114 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
Example
P-12 = 0; P-15 = 0
Figure 65: DI1 (Start), Two-wire control DI1 + DI2 = REV
The start enable via control signal terminal 3 (DI1) is always required for
operation:
Actuation
control signal terminal
3 (DI1) = Start enable, clockwise
rotating field (FWD)
Actuation control signal terminal 3 (DI1) plus control signal terminal 4
(DI2) = Start enable anticlockwise rotating field (REV)
The separate actuation of control signal terminal 4 (DI2) does not allow any
start enable.
23
Start
FWD/REV
+24 V
1
DI1 (Start)
FWD
DI2 (FWD/REV)
REV
f
out
(Motor)