9 Appendix
9.1 Special technical data
168 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
9.1.2 DC1-S2
9.1.3 DC1-12
Size Symbol Unit 4D3 7D0 011
Rated operational current  I
e
A 4.3 7.0 10.5
Overload current for 60 s every 600 s at 50 °C I
L
A 6.5 10.5 15.8
Apparent power at rated operation  230 V S kVA 1.71 2.79 4.38
240 V 1.79 2.91 4.57
Assigned motor rating  230 V P kW 0.37 0.75 1.1
HP 0.5 1 1.5
Power side (primary side):
Number of phases single-phase or two-phase
Rated operating voltage U
LN
V 200V -10% - 240V +10%, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current  I
LN
A 6.0 9.3 14.0
Minimum braking resistance R
B
Ω 47
Pulse frequency f
PWM
kHz 16 (adjustable 4 – 32)
Efficiency η 0.95 0.95 0.95
Size FS1 FS1 FS2
Size Symbol Unit 2D3 4D3 7D0 7D0 011 015
Rated operational current (I
e
)I
e
A 2.3 4.3 7.0 7.0 10.5 15
Overload current for 60 s every 600 s at 50 
°C
I
L
A 3.45 6.45 10.5 10.5 15.7 22.5
Apparent power in rated operation 400 V S kVA
0.92 1.71 2.79 2.79 4.38 5.98
480 V S kVA
0.96 1.79 2.91 2.91 4.57 6.24
Assigned motor rating 400 V P kW 0.37 0.75 1.5 1.5 2.2 4.0
460 V HP 0.5 1 2 2 3 5
Power side (Primary side)
Number of phases three-phase 
Rated voltage  U
LN
V 200 V - 10 % - 240 V + 10 %, 50/60 Hz
(180 - 264 V ±0 %, 48 - 62 Hz ±0 %)
Input current  I
LN
A 6.7 12.5 14.8 14.8 22.2 31.7
Minimum braking resistance R
B
Ω 47 47 47
Pulse frequency f
PWM
kHz 16 (adjustable 4 – 32)
Efficiency η 0.96 0.96 0.96 0.96 0.96 0.96
Fan (device-internal, temperature-controlled)
✓ ✓ ✓ ✓ ✓ ✓
Size FS1 FS1 FS1 FS2 FS3 FS3