6 Parameters
6.2 Digital and analog inputs
DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com 109
6.2.2 Analog Input (AI)
Control signal terminals 4 and 6 can be used as analog inputs (AI). The corre-
sponding signal range will depend on parameter P-16 for analog input AI1
and parameter P-47 for analog input AI2.
The reference potential for the two analog inputs (AI1, AI2) is 0 V (control sig-
nal terminals 7 and 9).
With the default settings, control signal terminal 6 (AI1) will be configured for
a setpoint voltage of 0 to +10 VDC and control signal terminal 4 as a digital
input (DI3).
Example
Desired options:
Analog input AI2 suitable for 4 to 20 mA with open-circuit monitoring
Switching the setpoint source between AI1 and AI2 via DI2.
Figure 60: Switching setpoint sources
Table 15: Analog and digital input wiring
DI1 (control signal terminal 2): FWD (Forward = Start enable clockwise
rotating field)
DI2 (control signal terminal 3): AI1/AI2 (change of setpoint source from
AI1 to AI2)
AI1 (control signal terminal 6): analog setpoint value 1
AI2 (control signal terminal 4): analog setpoint value 2
The function of control signal terminals 4 and 6 is defined by the
selection made in parameter P-15 and depends on the control
mode in parameter P-12.
P-15 DI1 DI2 AI1 AI2
4 0 = locked
1 = Start enable FWD
0 = AI1
1 = AI2
Setpoint value AI1
(0 - 10 V)
Setpoint value AI2
(4 - 20 mA)
+24 V
3
DI2
4
AI2
AI2
6
AI1
f-Soll 1
f-Soll 2
1
+24 V Out
< 100 mA
0...+10 V/
20 mA
4...
20 mA
P-12 = 0
P-15 = 7
P-47 =