9 Appendix
9.8 Motor reactors
182 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
9.8 Motor reactors
The motor reactor is in the output of the frequency inverter. Its rated opera-
tional current must always be greater than/equal to the rated operational cur-
rent of frequency inverter.
Figure 94: Motor reactors DX-LM3…
When multiple motors are connected in parallel in the motor
reactor, the rated operational current of the motor reactor must
be greater than the total current of all motors.
M
3 ~
DX-LM3...
U
max
f
PWM
f
2
U
max
Figure 95: Derating values for deviating installation altitudes and ambient air temperatures
0
0.5
0.6
0.7
0.8
0.9
1.0
1000 2000 3000 4000 5000
h [m]
I
I
e
40
0.5
0.6
0.7
0.8
0.9
1.0
45 50 55 60 65 70
Iso. class F
ta [°C]
I
I
e
Iso. class B
Further information and technical data on the motor
reactors of the DX-LM3… series is provided in instruc-
tional leaflet IL00906003Z.