7 Serial interface (Modbus RTU)
7.2 Modbus parameters
DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com 143
7.2 Modbus parameters
The following table 16 shows the Modbus parameters in the DC1 frequency
inverter.
RUN Indicates the access right during operation (FWD or REV)
- = No parameter change possible,
/ = Parameter change possible.
ro/rw Indicates the access right via the field bus
ro = Read only possible,
rw = Read and write possible.
Table 16: Modbus parameters
PNU
ID Access rights Designation Value range DS
RUN ro/rw
P-36 164 rw Frequency inverter slave
address
0 - 63 1
rw Baud rate 1 = OP-buS
2 = 9.6 kBit/s
3 = 19.2 kBit/s
4 = 38.4 kBit/s
5 = 57.6 kBit/s
6 = 115.2 kBit/s
OP-buS
rw TimedOut 0 - 3000 ms 3000 ms
P-12 140 rw Control level 0 = Control signal terminals (I/O)
1 = Keypad (KEYPAD FWD)
2 = Keypad (KEYPAD FWD/REV)
3 = Modbus, with internal acceleration and deceleration ramp
4 = Modbus, acceleration and deceleration ramps via bus
5 = PI controller with external actual value
6 = PI controller with external actual value and totalized value of
AI1
7 = CANopen, with internal acceleration and deceleration ramp
8 = CANopen, acceleration and deceleration ramps via bus
0