EasyManua.ls Logo

Eaton DC1-124D1FN-A20N - Page 189

Eaton DC1-124D1FN-A20N
194 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 Appendix
9.9 Sinusoidal filter
DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com 185
Table 29: Assignment of sinusoidal filters
Device type Rated opera-
tional current
I
e
for DC1
Assigned
sinusoidal
filter
I
e
f
2
U
k
U
e1
f
PWM1
U
e2
f
PWM2
[A] Part no. [A] [Hz] [%] [V] [kHz] [V] [kHz]
DC1-122D3… 2.3 DX-SIN3-004 4 0 - 150 7.5 0 - 440 3 -8 0 - 520 4 - 8
DC1-1D2D3 2.3
DC1-322D3… 2.3
DC1-432D2… 2.2
DC1-124D3… 4.3 DX-SIN3-010 10 0 - 150 7 0 - 440 3 -8 0 - 520 4 - 8
DC1-1D4D3 4.3
DC1-324D3… 4.3
DC1-324D1… 4.1
DC1-127D0… 7
DC1-1D5D8 5.8
DC1-327D0… 7
DC1-345D8… 5.8
DC1-349D5… 9.5
DC1-12011… 10.5 DX-SIN3-016 16.5 0 - 150 7.5 0 - 440 3 -8 0 - 520 4 - 8
DC1-32011… 10.5
DC1-12015… 15
DC1-32018… 18 DX-SIN3-023 23.5 0 - 150 8 0 - 440 3 -8 0 - 520 4 - 8
DC1-34018… 18
DC1-34024… 24 DX-SIN3-032 32 0 - 150 8.7 0 - 440 3 -8 0 - 520 4 - 8
Note:
Sinusoidal filter DX-SIN3… should only be operated with fixed pulse frequencies:
Range f
PWM1
at rated operating voltage U
e1
Range f
PWM2
at rated operating voltage U
e2

Table of Contents