2 Engineering
2.5 Motor and Application
DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com 39
Figure 12: Parallel connection of several motors to one frequency inverter
NOTICE
If multiple motors are connected in parallel to a single frequency
inverter, make sure to dimension the individual motors’ contac-
tors for utilization category AC-3.
The
motor contactor
must be
selected
according
to the
rated operational current of the motor
that will be connected.
The current consumption of all motors connected in parallel
must not exceed the frequency inverter’s rated output current
I
2N
.
When operating multiple motors in parallel, you cannot use the
frequency inverter’s electronic motor protection. You will have
to protect each motor individually with thermistors and/or a
current transformer-operated overload relay.
The use of motor-protective circuit-breakers at the output of fre-
quency inverters can result in motors being disconnected in an
undefined manner and is only possible in select applications.
When operating multiple single-phase AC motors in parallel
(only permissible with DC1-S… inverters), it is not permitted to
connect individual motors during operation!
Q11
F1
M1
Q12
F2
M2
Q13
F3
M3
U1 V1 W1 U1 V1 W1 U1 V1 W1
M
3
˜
M
3
˜
M
3
˜