2 Engineering
2.5 Motor and Application
DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com 41
Figure 15: V/Hz characteristic curve
for the rating plate of the motor from Figure 13
a Star connection: 400 V, 50 Hz
b Delta circuit: 230 V, 50 Hz
c Delta connection: 400 V, 87 Hz
The following Tabelle 3 shows the allocation of possible frequency inverters
depending on the mains voltage and the type of circuit.
Table 3: Assignments between frequency inverters and V/Hz characteristic curve
( Figure 15)
→
If using 2 pole motors (p = 1), the high speed of approximately
5,000 rpm must be taken into account (consult the manufac-
turer's specifications).
0
8750
400
U
2
[V]
f [Hz]
f
max
230
ac
b
Physical parameters DC1-124D3… DC1-324D3… DC1-342D2… DC1-344D1…
Rated operational current 4.3A 4.3A 2.2A 4.1A
Mains voltage 1AC230V 3AC 230V 3AC400V 3AC400V
V/f-characteristic curve ② ② ① ③
Motor circuit
Delta circuit (230 V) Delta circuit (230 V) Star-connected circuit
(400 V)
Delta circuit (230 V)
Motor current
3.5A 3.5A 2.0A 3.5A
Motor voltage 3AC 0-230V 3AC 0-230V 3AC 0-400V 3AC 0-400V
Motor speed 1430 min
-1
1430 min
-1
1430 min
-1
2474 min
-1 1)
Motor frequency 50 Hz 50 Hz 50 Hz 87 Hz
1)
1) Note the permitted limit values of the motor!