5 Error messages
5.1 Introduction
92 DC1 Frequency Inverter 10/12 MN04020003Z-EN www.eaton.com
E-triP External fault External shutdown (on digital input 3) External safety shutdown on digital input 3.
The normally-closed contact opened for some reason.
If a motor thermistor is connected, check whether the
motor is too hot.
SC-trF
Communication fault Communication loss error Check the communications connection between the
frequency inverter and external devices.
Make sure that each individual frequency inverter on
the network has a unique address.
P-loSS
Mains connection phase
fault
Input phase loss
Shutdown
A frequency inverter intended for use with a three-
phase supply has lost one of its input phases.
SPIn-F
Motor pick-up control function (for catching spin-
ning motors) failed
The motor pick-up control function did not determine
the motor speed.
dAtA-F
Data error Internal memory error Parameter not stored; default settings loaded back.
If the problem occurs again, please contact your
closest Eaton representative.
4-2OF Live zero error Analog input current outside range Make sure that the input current falls within the range
defined by P-16.
SC-FLt
Internal error Internal frequency inverter fault Please contact your closest Eaton representative.
FAULtY
Internal error Internal error Please contact your closest Eaton representative.
Indicator designation Possible cause Notes